Door control system - Door control system

Catalogue 2014/2015

Door control system Door control system ◾ Automation adjustable via CMC ◾ Manual and automatic door opening ◾ Automatic opening in case of power failure Note: To be connected at rear: – Door kit 2 door kits and 2 door kit extensions for LCP may be connected to one door control module – Door comfort handle or door switch Up to 2 door comfort handles/door switches may be connected for manual opening – Automatic door opening is achieved by connecting to the PU/PU Compact. Independently of this, the doors may be opened via the door comfort handle/door switch – In the event of a power failure, the doors will also open – Door kit extension for LCP must be backed up with a UPS – The front and rear door must always be opened Also required: – CMC III processing unit/compact, see page 450 – CAN bus sensor, see page 451 System diagram Door control system: ◾ A maximum of 16 door control systems per processing unit ◾ A maximum of 2 door control systems may be connected per processing unit 1 Door control module 2 3 4 CMC III – Processing Unit – Processing Unit Compact CAN bus sensor Door kit Door comfort handles Door kit extension for LCP min. 800 mm enclosure depth Rittal Catalogue 34/IT infrastructure 459