Total cooling output 291 – 481 kW

Catalogue 2014/2015

Chillers for IT cooling Total cooling output 291 – 481 kW Model No. Packs of 3232.841 3232.851 3232.861 3232.871 3232.881 Page Total cooling output kW 291 326 387 430 481 Width mm 2200 2200 2200 2200 2200 Height mm 2450 2450 2450 2450 2450 Depth mm 3400 3400 4250 4250 4250 Rated operating voltage V, ~, Hz 400, 3~, 50 400, 3~, 50 400, 3~, 50 400, 3~, 50 400, 3~, 50 Air throughput at max. cooling output m³/h 71500 70200 106200 104100 102000 Power consumption kW 93 106 121 141 159 Rated current max. A 203 225 293 307 336 Refrigerant R410a R410a R410a R410a R410a Permissible operating pressure (p. max.) bar 45 45 45 45 45 Operating temperature range -20°C...+43°C -20°C...+43°C -20°C...+43°C -20°C...+43°C -20°C...+43°C Temperature of liquid +5°C...+15°C +5°C...+15°C +5°C...+15°C +5°C...+15°C +5°C...+15°C Pump capacity l/min 810 810 1200 1200 1200 Pump pressure bar 2.5 2.5 2.5 2.5 2.5 Number of cooling circuits 2 2 2 2 2 Steel tank, with 10 mm condensate insulation ◾ ◾ ◾ ◾ ◾ Tank capacity l 700 700 700 700 700 Water connection 3" internal thread 3" internal thread 4" internal thread 4" internal thread 4" internal thread Weight as delivered kg 2700.0 2800.0 3100.0 3000.0 3600.0 Operating weight kg 3400.0 3500.0 3800.0 3700.0 4300.0 Colour RAL 9002 RAL 9002 RAL 9002 RAL 9002 RAL 9002 New RiMatrix S see page 398 Rittal Catalogue 34/IT infrastructure 443


Catalogue 2014/2015
To see the actual publication please follow the link above