Air/air heat exchangers - Specific thermal output 66 W/K, roof-mounted

Catalogue 2014/2015

Air/air heat exchangers Climate control accessories Page 369 Therm software Page 385 Colour: – RAL 7035 – RAL 9005 Protection category IP to IEC 60 529: – Internal circuit IP 54 Supply includes: – Complete unit ready for connection – The fans are connected via two 3-wire connection cables, with wire end ferrules Note: – For precise temperature control inside the enclosure, we recommend the enclosure internal thermostat, the digital enclosure internal temperature display and thermostat or the speed control Technical details: Available on the Internet Specific thermal output 66 W/K, roof-mounted Model No. Packs of 3248.000 Page Rated operating voltage V, ~, Hz 230, 1~, 50/60 Specific thermal output W/K 66 No. of fans 2 Max. rated current per fan A 0.45 / 0.55 Pre-fuse A 4 Output per fan W 75 Air throughput of fans (unimpeded air flow), external circuit m³/h 965 Air throughput of fans (unimpeded air flow), internal circuit m³/h 965 Width mm 595 Height mm 362 Depth mm 440 Operating temperature range -5°C...+55°C Type of electrical connection Connection cable Weight kg 16.8 Accessories Digital enclosure internal temperature display and thermostat 1 pc(s). 3114.200 379 Enclosure internal thermostat 1 pc(s). 3110.000 379 Hygrostat 1 pc(s). 3118.000 380 Speed control 1 pc(s). 3120.200 381 330 Rittal Catalogue 34/Climate control