Ri4Power Table 38: Rated currents Inc for moulded-case circuit-breakers Schneider Electric Brand Schneider Electric Rated current Inc with consideration Minimum compartment dimensions Minimum In of protection category and cooling connection circuit- Forced Forced cross- Type breaker ventilation ventilation 3-pole version 4-pole version section IP 2X IP 2X IP 43 IP 54 IP 54 Width Height Width Height Top A A A A A A mm mm mm mm mm2 NSX100 16 14 14 14 14 14 400 150 400 200 2.5 NSX100 25 23 22 22 23 22 400 150 400 200 4 NSX100 32 29 28 28 29 28 400 150 400 200 6 NSX100 40 36 35 35 36 35 400 150 400 200 10 NSX100 50 45 44 44 45 44 400 150 400 200 10 NSX100 63 57 55 55 57 55 400 150 400 200 16 NSX100 80 72 70 70 72 70 400 150 400 200 25 NSX100 100 90 87 87 90 87 400 150 400 200 50 NSX160 80 72 70 70 72 70 400 200 400 300 35 NSX160 100 90 87 87 90 87 400 200 400 300 50 NSX160 125 113 109 109 113 109 400 200 400 300 70 NSX160 160 144 139 139 144 139 400 200 400 300 95 NSX250 125 113 109 109 113 109 400 300 400 300 70 NSX250 160 144 139 139 144 139 400 300 400 300 95 NSX250 200 182 174 174 182 174 400 300 400 300 120 NSX250 250 228 218 218 228 218 600 300 600 300 150 NSX400 400 368 356 356 368 356 600 300 600 300 2 x 150 NSX630 630 567 504 498 567 504 600 400 600 400 2 x 150 2 - 85 Rittal Technical System Catalogue/Power distribution