Ri4Power Table 37: Rated currents Inc for moulded-case circuit-breakers Mitsubishi Brand Mitsubishi Rated current Inc with consideration Minimum compartment dimensions Minimum In of protection category and cooling connection circuit- Forced Forced cross- Type breaker ventilation ventilation 3-pole version 4-pole version section IP 2X IP 2X IP 43 IP 54 IP 54 Width Height Width Height Top A A A A A A mm mm mm mm mm2 NF32-SW 16 14 14 14 14 14 400 150 400 150 2.5 NF32-SW 20 18 17 17 18 17 400 150 400 150 2.5 NF32-SW 25 23 22 22 23 22 400 150 400 150 4 NF32-SW 32 29 28 28 29 28 400 150 400 150 6 NF400-HEW 400 368 356 356 368 356 600 300 600 300 2 x 150 NF400-REW 400 368 356 356 368 356 600 300 600 300 2 x 150 NF400-SEW 400 368 356 356 368 356 600 300 600 300 2 x 150 NF400-UEW 400 368 356 356 368 356 600 600 800 600 2 x 150 NF63 .... 3 3 3 3 3 3 400 150 400 150 1.5 NF63 .... 4 4 3 3 4 3 400 150 400 150 1.5 NF63 .... 6 5 5 5 5 5 400 150 400 150 1.5 NF63 .... 10 9 9 9 9 9 400 150 400 150 1.5 NF63 .... 16 14 14 14 14 14 400 150 400 150 2.5 NF63 .... 20 18 17 17 18 17 400 150 400 150 4 NF63 .... 25 23 22 22 23 22 400 150 400 150 6 NF63 .... 32 29 28 28 29 28 400 150 400 150 6 NF63 .... 40 36 35 35 36 35 400 150 400 150 10 NF63 .... 50 45 44 44 45 44 400 150 400 150 10 NF63 .... 63 57 55 55 57 55 400 150 400 150 16 NF630.... 630 567 504 498 567 504 600 600 600 600 2 x 240 NF800-UEW 800 720 640 640 640 640 600 600 600 600 50 x 10 Rittal Technical System Catalogue/Power distribution 2 - 84